Date:04-29-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:3700909SYSTEM NAME:JULIAN COMMUNITY SERVICES DISTRICTCOUNTY:SAN DIEGO 
SOURCE NO.:002SOURCE NAME:TREATMENT FOR ALL SYSTEM WELLSSOURCE CLASS:OTHRSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA3700909_002_002 SECONDARY/GP-202612 1928 ALKALINITY, BICARBONATE 90.000 5.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1919 CALCIUM 28.000 1.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1929 ALKALINITY, CARBONATE < 5.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1017 CHLORIDE 14.000 0.500 MG/L 500 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1905 COLOR < 5.000 UNITS 15 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1022 COPPER, FREE < 50.000 UG/L 1000 50 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 2905 FOAMING AGENTS (SURFACTANTS) < 0.050 MG/L .5 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1915 HARDNESS, TOTAL (AS CACO3) 106.000 5.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1021 HYDROXIDE AS CALCIUM CARBONATE < 5.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1028 IRON < 100.000 UG/L 300 100 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1031 MAGNESIUM 8.800 1.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1032 MANGANESE < 20.000 UG/L 50 20 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1920 ODOR < 1.000 TON 3 1 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1925 PH 7.750 1.680 pH 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1050 SILVER < 10.000 UG/L 100 10 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1052 SODIUM 22.000 1.000 MG/L 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1064 CONDUCTIVITY @ 25 C UMHOS/CM 330.000 10.000 UMHO/CM 1600 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1055 SULFATE 37.000 5.000 MG/L 500 .5 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1930 TDS 200.000 10.000 MG/L 1000 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 0100 TURBIDITY < 1.000 NTU 5 .1 12-27-2023 36 2026/12
CA3700909_002_002 SECONDARY/GP-202612 1095 ZINC < 50.000 UG/L 5000 50 12-27-2023 36 2026/12
CA3700909_002_002 INORGANIC-203212 1094 ASBESTOS < 0.200 MFL 7 .2 12-27-2023 108 2032/12
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.